E
Integrity
The door contains the fire. No flames or hot gases pass through to the unexposed side for the rated duration. Every Fort firebreak product is integrity-rated.
The LPCB standard for firebreak doors and shutters. Three Fort products are certified, with fire ratings from EI₂30 right up to EI₁120-C0. Tested to EN 1634-1, classified to EN 13501-2, audited and listed by LPCB on RedBook Live.
LPS 1056 certifies firebreak doors and shutters against the European fire-resistance standards. It tests how long a door assembly contains fire and limits heat transfer to the unexposed side. The rating you’ll see on a certificate (EI₂30, EI₁120-C0) follows the same notation used across UK and EU fire compartmentation.
Fort holds LPS 1056 against three products in a single certificate, 1607a. Each product gets its own sub-listing on RedBook Live, with a separate listing for each Fort Vault FB4 rating variant. Two of the three products also carry LPS 1175 forced-entry certification, which is what makes them useful where the fire compartment line and the security perimeter happen to be the same wall.
– 01 / 04
Reading the rating
The fire rating on each Fort certificate is a compact string. Here’s how to read it, piece by piece, using EI₁120-C0 as the example.
E
The door contains the fire. No flames or hot gases pass through to the unexposed side for the rated duration. Every Fort firebreak product is integrity-rated.
I₁ / I₂
The door also limits heat transfer. I₁ is the stricter test (peak temperature rise on any single point). I₂ is the average. I₁ ratings sit above I₂ on the same duration.
120
Duration of the rated performance under EN 1634-1 furnace conditions. Fort holds 30 minutes at the entry level, up to 120 minutes on the Fort Vault FB4.
C0
Self-closing performance classification. C0 means the rating is valid without a specific self-closing cycle requirement on top.
So EI₁120-C0 reads as: integrity-rated, with stricter I₁ insulation, for 120 minutes, with C0 cycle classification. It’s the highest fire rating in the Fort range.
– 02 / 04
Certified products
All three are single-leaf, insulated, hinged firebreak doorsets. Fort 001 and Fort 002LP2S each hold one fire rating. The Fort Vault FB4 holds three separate ratings, each listed as its own entry on RedBook Live.
01 / Product
Cert 1607a/01
Single-leaf insulated firebreak doorset. Entry-level fire rating for compartmentation in commercial and residential buildings. The original Fort fire product, certified since the company’s first LPCB audit.
Configuration
Single leaf, hinged, active
Maximum size
2059mm H × 934mm W (1.92m²)
Glazing
Unglazed
Other certifications
Fire only
02 / Product
Cert 1607a/02
Single-leaf insulated firebreak doorset. Same EI₂30 fire integrity as Fort 001, but this is the dual-certified variant – the same product also holds LPS 1175 SR2 forced-entry certification.
Configuration
Single leaf, hinged, active
Maximum size
2059mm H × 934mm W (1.92m²)
Glazing
Unglazed
Other certifications
03 / Product
Cert 1607a/03
Single-leaf insulated firebreak doorset. The headline fire product, certified across three rating variants. Same envelope, three certified configurations – each independently tested and listed on RedBook Live.
Configuration
Single leaf, hinged, active
Maximum size
2731mm H × 1125mm W (2.79m²)
Glazing
Unglazed
Other certifications
Triple-cert worth flagging. Fort Vault FB4 is the only product in the entire Fort range that holds three independent certifications: LPS 1175 SR4 forced-entry, LPS 1056 fire integrity up to EI₁120-C0, and FB4 ballistic resistance. Useful where the fire compartment line, the security perimeter, and the ballistic threat all sit on the same opening – data centre critical rooms, embassies, MOD List X.
– 03 / 04
Documents
Cert 1607a is one certificate covering three products. RedBook Live splits it into five separate listings because Fort Vault FB4 holds three distinct fire rating variants under the same cert reference. Each one is verifiable independently.
01
Cert 1607a/01
02
Cert 1607a/02
03
Cert 1607a/03
04
Cert 1607a/03
05
Cert 1607a/03
Need a fire cert for a tender?
Tell us the project and the rating you’re specifying, we’ll send the current cert revision the same working day.
Fort manufactures, the customer brands sell. Project surveys, BIM objects, and project-specific fire certificates are routed through whichever brand fits the project type. Pick yours.